Rhoss 60 kW heat pump
Technical data:
Design parameters
COP (gross) 3.03
HEATING POWER [kW]: 61.6
Cooling POWER [kW]: 58.9
Fans
Type: Axial
Number of fans: 2
Consumption of each [kW]: 0.6
Air flow [m³ / h]: 20200
Machine configuration
Refrigerant: R410A
Refrigerant charge [kg]: 23.1
Global Warming Potential (GWP): 2088
CO2 equivalent [tonnes]: 48.2
Scroll compressors
Number of compressors: 2
Number of independent circuits: 1
Noise
No additional options for noise reduction device
Sound power level [dBA]: 81
Sound pressure level (5m) [dBA]: 57
Electrical data
Total electric power [kW]: 22.3
Nominal pump power [kW]: 0.7
Power consumed by the pump [kW]: 0.7
Electric power supply [V-ph-Hz]: 400-3-N-50
Auxiliary power [V-ph-Hz]: 230-1-50
Nominal current [A]: 41.3
Maximum current [A]: 57.1
Inrush current [A]: 181.1
Size and weight
Width [mm]: 2315
Height [mm]: 1570
Depth [mm]: 1000
Own weight [kg]: 635
Primary exchanger inlet / outlet connections: 2 ''